Notes:
1. Values have been calculated as described in the‘European Recommendations for the Design of
Sandwich Panels’ (ECCS), taking imposed loads,
temperature and creep into account.
* The values shown are SLS loads. (Service limit
state or “Working” loads)
2. For each value individual and combined load cases
with appropriate load factors and temperatures
have been considered.
3. The table is for medium and light coloured panels,
as recommended for roofing purposes.
4. The following deflection limits have been used:
Downward loading L/200
Suction loading L/150
5. For intermediate values linear interpolation may
be used.
6. The actual wind suction load resisted by the panel
is dependant on the number of fasteners used and
the material of the purlin. The fastener calculation
should be carried out in accordance with the
appropriate standard. For further advise please
contact Ward Technical Services.
7. The allowable steelwork tolerance between
bearing planes of adjacent purlins is +/-5mm.
8. Load span tables for panel specifications not
shown are available from Ward Technical Services. |